ABB AX411/50001 Analog module industrial system controller

Numer modelu: AX411/50001
Manufacturer: ABB
Quantity:ten
Serial ports: 2
Network ports: 4
Port isolation: 280 VDC
Weight : 3 Kg
Shipping Weight : 4 Kg

Category:
Whatsapp:+86 15359293870
WeChat:+86 18106937731
                E-mail:geabbdcs@gmail.com
Contacts:kelly CHEN

Description

Manufacturer ABB
Brand ABB
Series module
Part Number AX411/50001
Product Type module
Quality 100% New Original
Stock In stock
Delivery time 1-3 days after Payment
After-sales Service Have
Warranty 1 year
Shipping term DHL / FEDEX/ EMS /UPS/TNT/EMS

 

Packaging details: if you need an urgent delivery order, please feel free to contact us, and we will do our best to meet your needs.

Price problem: if you find that other suppliers offer cheaper prices for the same product, we are also willing to provide you with reference prices and give you further discounts.

 

 Safe torque off
For the drive to start, both connections (OUT1 to IN1 and IN2) must be closed. By
default, the terminal block has jumpers to close the circuit. Remove the jumpers
before connecting an external Safe torque off circuit to the drive.
For information on the implementation of Safe torque off function, see chapter The
Safe torque off function (page 141).
 Safety functions (X12)
See the connections to the safety functions module on page 85 and FSO-12 user’s
manual (3AXD50000015612 [English])
 Control unit connector data
Power supply
(XPOW)
Connector pitch 5 mm, wire size 2.5 mm2
24 V (±10%) DC, 2 A
External power input. Two supplies can be connected to BCU for
redundancy.
Relay outputs RO1…RO3
(XRO1…XRO3)
Connector pitch 5 mm, wire size 2.5 mm2
250 V AC / 30 V DC, 2 A
Protected by varistors
+24 V output
(XD24:2 and XD24:4)
Connector pitch 5 mm, wire size 2.5 mm2
Total load capacity of these outputs is 4.8 W (200 mA / 24 V)
minus the power taken by DIO1 and DIO2.
Digital inputs DI1…DI6
(XDI:1…XDI:6)
Connector pitch 5 mm, wire size 2.5 mm2
24 V logic levels: “0” < 5 V, “1” > 15 V
Rin: 2.0 kohm
Input type: NPN/PNP (DI1…DI5), NPN (DI6)
Hardware filtering: 0.04 ms, digital filtering up to 8 ms
DI6 (XDI:6) can alternatively be used as an input for a PTC
thermistor.
“0” > 4 kohm, “1” < 1.5 kohm
Imax: 15 mA (DI1…DI5), 5 mA (DI6)
Start interlock input DIIL
(XD24:1 [ZCU])
Connector pitch 5 mm, wire size 2.5 mm2
24 V logic levels: “0” < 5 V, “1” > 15 V
Rin: 2.0 kohm
Input type: NPN/PNP
Hardware filtering: 0.04 ms, digital filtering up to 8 ms