Brand: ABB
Model: SPAD346C2
Product Name: Stabilized Differential Protection Relay
Dimension: 222 mm × 122 mm × 185 mm
Weight: 5.8 kg
Origin: Finland
HS Code: 85364900
Operating Temperature: -10°C to +55°C
Storage Temperature: -40°C to +70°C
Auxiliary Supply Voltage: 80–265 V AC / DC or 18–80 V DC (version dependent)
Rated Frequency: 50 Hz / 60 Hz selectable
Rated Current Input: 1 A or 5 A CT, switchable
Digital Input: 5 programmable binary control inputs
Relay Output: 4 heavy-duty trip relays for circuit breaker tripping; 5 signal alarm relays
Contact Rating: 250 V AC/DC, continuous 5 A
Communication: SPA bus / RS485 serial interface
Mounting: Panel flush mounting in switchgear cabinet
Certification: CE, EMC compliant
Protection Class: IP20 (when installed inside cabinet)
-
SPAD346C2
Features and Functions
Percentage stabilized differential protection for transformer internal short-circuit, inter-turn fault and earth fault
Second harmonic restraint to prevent false tripping during magnetizing inrush
Fifth harmonic restraint for blocking overexcitation mal-operation
Three-phase multi-stage overcurrent protection and two-stage backup earth fault protection
Built-in circuit breaker failure protection with adjustable delay time
Integrated disturbance recorder for waveform and event recording
Wide CT ratio correction range, digital parameter setting
5 programmable binary inputs for Buchholz relay, temperature alarm and blocking signals
Continuous hardware and software self-supervision with internal fault alarm
Local parameter setting and measurement display via front panel
Remote communication for data reading, fault log and parameter modification
High anti-interference performance for harsh substation electromagnetic environment
Event log and trip record for fault analysis
FQA
Q1: What is ABB SPAD346C2?
A1: It is a stabilized differential protection relay in SPACOM series, used as main differential protection for two-winding transformers and generator-transformer units.
Q2: Is SPAD346C2 still in production?
A2: SPAD346C series has been discontinued by ABB. It is mainly supplied as original surplus, used and refurbished spare parts for maintenance.
Q3: What is the core anti-mal-operation function?
A3: It uses second harmonic restraint for inrush blocking and fifth harmonic restraint for transformer overexcitation blocking.
Q4: What signals can be connected to binary inputs?
A4: The 5 programmable inputs can receive Buchholz relay alarm, winding temperature signal, protection blocking and reset signals.
Q5: Does it have disturbance recording function?
A5: Yes, it has built-in disturbance recorder to capture analog and digital fault signals for post-fault analysis.
-
SPAD346C2
♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦
Shipping:
1. Your item will be shipped to all countries via EMS, unless one country cannot be shipped via EMS. We will choose DHL, UPS, or FedEx. Please leave us your phone number.
2. We will ship the product to you on the same day or within 1-2 working days after receiving your payment. The shipping time depends on the country/region where you reside, the customs and habits of your country/region, and especially during peak hours.
3. Assuming (assuming) that the item requires payment of tariffs from your country, the buyer is obligated. We are not responsible for any taxes or customs fees in your country/region.
Return Policy:
1. Please contact us before returning the item.
2. The buyer should inform the seller of all returned items within 7 days after receiving the package. We reserve the right to reject any request to inform the seller for more than 7 days.
3. Returned products must have all original packaging and be in good condition.
Response policy:
If you are satisfied with the purchase, please leave us an active response.
2. If you have any questions about the outcome of the transaction or product, please contact us first and we will do our best to satisfy you!
3. Please do not reply with negative feedback before contacting us!