ProSoft MVI56E-DNPNET DNP3 Ethernet Communication Module Product Specification
Brand: ProSoft Technology
Model: MVI56E-DNPNET
Product Name: Enhanced DNP3 Ethernet Communication Module for ControlLogix
Origin: United States
HS Code: 85389000
Dimension: 120 mm × 50 mm × 128 mm
Weight: 0.36 kg
Operating Temperature: 0°C to +60°C
Storage Temperature: -40°C to +85°C
Rated Supply Voltage: Powered by ControlLogix backplane, 5.1 V DC nominal
Rated Operating Current: 800 mA @ 5.1 V DC, 3 mA @ 24 V DC
Relative Humidity: 5% to 95%, non-condensing
Ingress Protection: IP20 for cabinet installation
Single slot form factor compatible with 1756 ControlLogix local and remote racks
-
MVI56E-DNPNET
10/100 Base-T Ethernet RJ45 port with auto MDI/MDI-X crossover detection
Supports DNP3 client and server modes simultaneously
Supports DNP3 secure authentication (DNP3-SA) with AES-256 encryption
Supports Report by Exception (RBE) for efficient event transmission
High-resolution millisecond timestamp for sequence-of-event records
Large configurable DNP3 database for binary, analog and counter data points
Built-in 4‑character scrolling alpha-numeric LED status display
Front panel LED indicators for module, application and error status
Supports CIPconnect pass-through diagnostics over EtherNet/IP
Configuration via ProSoft Configuration Builder (PCB) software and Studio5000 AOI
Backward compatible with legacy MVI56-DNPSNET module
Class I Division 2 and ATEX Zone 2 hazardous location certification
Operational shock rating of 30 g, non-operational shock rating of 50 g
Vibration resistance rated at 5 g from 10 Hz to 150 Hz
Hot swappable under qualified redundant rack configuration
Built-in real-time clock with backup battery for timestamp retention
-
MVI56E-DNPNET
ProSoft MVI56E-DNPNET FAQ
Q1: What is the difference between MVI56E-DNPNET and MVI56-DNPSNET?
A1: MVI56E-DNPNET is the enhanced E-series version, with faster processing, DNP3 secure authentication support and web-based diagnostics. MVI56-DNPSNET is the older generation DNP3 server-only module without these upgraded security functions.
Q2: Can MVI56E-DNPNET work as both DNP3 master and slave at the same time?
A2: Yes, this module supports concurrent DNP3 client (master) and DNP3 server (slave) operation, which allows bidirectional data exchange between the ControlLogix PLC and multiple DNP3 field devices.
Q3: Does MVI56E-DNPNET need an external power supply?
A3: No external power supply is required. The module draws all operating power directly from the ControlLogix 1756 chassis backplane.
-
MVI56E-DNPNET
♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦
Shipping:
1. Your item will be shipped to all countries via EMS, unless one country cannot be shipped via EMS. We will choose DHL, UPS, or FedEx. Please leave us your phone number.
2. We will ship the product to you on the same day or within 1-2 working days after receiving your payment. The shipping time depends on the country/region where you reside, the customs and habits of your country/region, and especially during peak hours.
3. Assuming (assuming) that the item requires payment of tariffs from your country, the buyer is obligated. We are not responsible for any taxes or customs fees in your country/region.
Return Policy:
1. Please contact us before returning the item.
2. The buyer should inform the seller of all returned items within 7 days after receiving the package. We reserve the right to reject any request to inform the seller for more than 7 days.
3. Returned products must have all original packaging and be in good condition.
Response policy:
If you are satisfied with the purchase, please leave us an active response.
2. If you have any questions about the outcome of the transaction or product, please contact us first and we will do our best to satisfy you!
3. Please do not reply with negative feedback before contacting us!
Related models: