Description
Operation Manual for ISH070/60011/0/0/00/0/00/01/00
- Safety Precautions
Ensure the power supply is disconnected before installation, wiring, or maintenance to prevent electric shock.
Verify that the operating voltage, input/output signal ranges, and environmental conditions (temperature: -20°C to +60°C; humidity: 5-95% non-condensing) comply with the specifications in ABB’s official datasheet.
Avoid installation in areas with strong electromagnetic interference, vibration, or corrosive gases.
- Mounting Procedure
Align the converter with a standard DIN 35mm rail (compatible with TS35/7.5 or TS35/15 rails).
Slide the converter onto the rail until it locks into place. Ensure a secure fit without looseness.
Maintain a minimum clearance of 5mm between adjacent devices for proper heat dissipation.
- Wiring Instructions
3.1 Power Supply Connection
Connect the power supply to terminals 1 (Positive, +) and 2 (Negative, -). The rated voltage for this model is 24VDC (18-30VDC, as per ABB’s specifications).
Ensure correct polarity; reverse polarity may damage the device.
3.2 Input Signal Wiring
Connect the analog input signal (e.g., 4-20mA, 0-10V) to terminals 3 (Input +) and 4 (Input -).
For 2-wire transmitter applications, ensure the loop power supply is properly configured (if applicable).
3.3 Output Signal Wiring
Connect the isolated output signal to terminals 5 (Output +) and 6 (Output -). The output type (e.g., 4-20mA) is preconfigured per the model suffix “60011”.
Tighten terminal screws to 0.5-0.8 N·m to avoid poor contact.
- Power-Up and Configuration
Turn on the power supply. The green LED indicator (Power) on the front panel will illuminate, indicating successful power-on.
The device operates in default mode (preconfigured per order specifications) without additional programming for standard applications.
For parameter adjustment (e.g., signal scaling, filter settings), use ABB’s optional configuration software (via RS485 port, terminals 7 and 8) or a handheld programmer. Follow the steps below for software configuration:
- Install ABB’s “Signal Converter Configuration Tool” (available on ABB’s official website).
- Connect the PC to the converter via an RS485-to-USB adapter (terminals 7: RS485+, 8: RS485-).
- Launch the software, select the communication port and baud rate (default: 9600bps), and establish a connection.
- Modify parameters (e.g., input range, output scaling) as required, then save and apply the settings.
- Operation and Monitoring
After configuration, the yellow LED indicator (Signal) will illuminate, indicating valid input/output signal transmission.
Monitor the LED status:
Flashing red LED: Fault (e.g., overrange input, power supply failure). Refer to the ABB troubleshooting guide for resolution.
Steady green LED: Normal operation.
Verify the output signal with a multimeter to ensure it matches the expected range.
- Maintenance and Troubleshooting
Perform periodic inspections (every 6 months) to check wiring tightness and LED status.
Clean the device surface with a dry cloth; avoid using corrosive cleaners.
Common troubleshooting steps:
No power (LED off): Check power supply voltage and wiring polarity.
No output signal: Verify input signal integrity and output wiring.
Signal interference: Ensure proper grounding (terminal 9: Ground) and check for electromagnetic interference sources.
- Dismantling Procedure
Disconnect the power supply and all wiring.
Press the release tab on the top of the converter and slide it upward to remove it from the DIN rail.




ISH070/60011/0/0/00/0/00/01/00 PDF
ISH070 60011 0 0 00 0 00 01 00
♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦
Shipping:
1. Your item will be shipped to all countries via EMS, unless one country cannot be shipped via EMS. We will choose DHL, UPS, or FedEx. Please leave us your phone number.
2. We will ship the product to you on the same day or within 1-2 working days after receiving your payment. The shipping time depends on the country/region where you reside, the customs and habits of your country/region, and especially during peak hours.
3. Assuming (assuming) that the item requires payment of tariffs from your country, the buyer is obligated. We are not responsible for any taxes or customs fees in your country/region.
Return Policy:
1. Please contact us before returning the item.
2. The buyer should inform the seller of all returned items within 7 days after receiving the package. We reserve the right to reject any request to inform the seller for more than 7 days.
3. Returned products must have all original packaging and be in good condition.
Response policy:
If you are satisfied with the purchase, please leave us an active response.
2. If you have any questions about the outcome of the transaction or product, please contact us first and we will do our best to satisfy you!
3. Please do not reply with negative feedback before contacting us!