Description
IS220PDIAH1B and IS220PDIOH1A Installation Steps
## 1. Pre-Installation Preparation
– **Compatibility Verification**: Confirm that IS220PDIAH1B (digital input module) and IS220PDIOH1A (digital output module) are compatible with the target GE Mark VIe control system by referencing the system’s hardware compatibility list.
– **Module Inspection**: Check both modules for physical defects, including bent pins in connectors, cracks in the housing, or loose components. Ensure terminal blocks and labeling are intact.
– **Tool and Safety Preparation**: Gather tools: Phillips screwdriver, torque wrench (0.5–0.8 N·m range), anti-static wristband, and wire strippers. Prepare personal protective equipment (PPE) including insulated gloves and safety glasses.
– **Environmental Check**: Ensure the installation area meets operating conditions: temperature (-5°C to +60°C), humidity (5–95% non-condensing), and minimal vibration. Verify the chassis is properly grounded.
## 2. Mounting the Modules
– **System Power Down**: De-energize the Mark VIe chassis and implement lockout/tagout (LOTO) procedures to prevent electrical hazards.
– **Anti-Static Protection**: Wear the anti-static wristband and connect it to a verified ground point on the chassis to protect sensitive electronics.
– **Chassis Installation**:
– Align the IS220PDIAH1B (digital input) and IS220PDIOH1A (digital output) modules with their respective slots in the chassis, ensuring the guide rails engage with the module edges.
– Slide each module firmly into the slot until the backplane connector fully mates (a subtle click may be felt).
– Secure each module using the front-panel mounting screws, tightening to 0.6 N·m. Do not over-tighten, as this may damage the chassis or module.
## 3. Wiring Connections
– **Reference Documentation**: Use the GE Mark VIe wiring diagram to identify terminal assignments for power, inputs, and outputs on both modules.
– **IS220PDIAH1B (Digital Input) Wiring**:
– Connect field devices (e.g., limit switches, proximity sensors) to the “DI” terminals. Use 24V DC-compatible shielded cables.
– Strip wire ends to 6–7mm, insert into terminal blocks, and tighten screws to 0.3–0.4 N·m. Ensure no stray strands cause short circuits.
– Ground cable shields at the module end using the dedicated grounding terminal (marked “SHLD”).
– **IS220PDIOH1A (Digital Output) Wiring**:
– Connect load devices (e.g., solenoids, indicator lights) to the “DO” terminals, ensuring the total load does not exceed the module’s rating (typically 2A per channel at 24V DC).
– Use appropriately sized wires (minimum 22 AWG) and install inline fuses for overcurrent protection.
– Secure wires to terminals with the same torque as input connections (0.3–0.4 N·m).
– **Power Confirmation**: Both modules receive power via the chassis backplane; no external power wiring is required. Verify backplane voltage (24V DC ±10%) with a multimeter before proceeding.
## 4. Post-Installation Checks
– **Connection Verification**: Visually inspect all wiring to ensure correct terminal assignments, tight connections, and proper routing (avoiding sharp edges or heat sources).
– **Mechanical Security**: Confirm modules are fully seated in the chassis and mounting screws are properly torqued.
– **Insulation Test**: Use a megohmmeter to check insulation resistance between terminals and ground (minimum 100 MΩ at 500V DC) to detect hidden shorts.
## 5. System Integration and Validation
– **Power Restoration**: Remove LOTO devices and power on the chassis. The modules’ status LEDs will blink during initialization (30–60 seconds) and illuminate steady green once operational.
– **Configuration Validation**: Launch GE ToolboxST software, connect to the controller, and verify the modules are detected in the hardware configuration.
– **Function Testing**:
– For IS220PDIAH1B: Activate connected input devices (e.g., toggle switches) and confirm status updates in ToolboxST.
– For IS220PDIOH1A: Trigger outputs via the software and verify connected loads respond correctly (e.g., lights illuminate, solenoids actuate).
## 6. Safety Notes
– Never work on live wiring. Always de-energize the system and use LOTO during installation or maintenance.
– Do not exceed the modules’ current or voltage ratings, as this may cause permanent damage or fire risk.
– Replace damaged modules only with genuine GE parts to maintain system integrity and s

IS220PDIAH1B -IS220PDIOH1A PDF
♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦
Shipping:
1. Your item will be shipped to all countries via EMS, unless one country cannot be shipped via EMS. We will choose DHL, UPS, or FedEx. Please leave us your phone number.
2. We will ship the product to you on the same day or within 1-2 working days after receiving your payment. The shipping time depends on the country/region where you reside, the customs and habits of your country/region, and especially during peak hours.
3. Assuming (assuming) that the item requires payment of tariffs from your country, the buyer is obligated. We are not responsible for any taxes or customs fees in your country/region.
Return Policy:
1. Please contact us before returning the item.
2. The buyer should inform the seller of all returned items within 7 days after receiving the package. We reserve the right to reject any request to inform the seller for more than 7 days.
3. Returned products must have all original packaging and be in good condition.
Response policy:
If you are satisfied with the purchase, please leave us an active response.
2. If you have any questions about the outcome of the transaction or product, please contact us first and we will do our best to satisfy you!
3. Please do not reply with negative feedback before contacting us!
More models available: