Description
TOSHIBA GPF611S VFD – Common Fault Codes & Resolution Procedures
1. Critical Fault Indications
| Fault Code | LED Status | Probable Cause | Immediate Actions |
|---|---|---|---|
| F05 | Red LED + Audible Alarm | DC Bus Overvoltage (>800VDC) | 1. Check input voltage (Allowable: 380VAC±15%) 2. Inspect regenerative resistor (≥500Ω @ 300W) 3. Extend deceleration time (Parameter C01-08) |
| F11 | Red Flashing (1Hz) | Output Overcurrent (>150% rated) | 1. Verify motor insulation (Megger ≥100MΩ @ 500VDC) 2. Check phase-to-phase resistance imbalance (<2%) 3. Disable unnecessary torque boost (A01-04=0) |
| F09 | Red Steady | Heatsink Overtemperature (>85°C) | 1. Clean air vents (40% blockage threshold) 2. Verify cooling fan operation (24VDC @ 0.18A) 3. Reduce carrier frequency (C02-01 ≤4kHz) |
2. Performance Degradation Issues
Symptom: Motor vibration/hunting at low speeds
- Solution:
- Enable Auto-Tuning II (Procedures):
- Set
A01-00=1(Rotational Auto-Tuning) - Press
RUNfor 10s untilTUNEflashes
- Set
- Adjust slip compensation (C03-05=1.5~2.0)
- Verify encoder feedback (if used): PG card pulse loss ≤0.1%
- Enable Auto-Tuning II (Procedures):
Symptom: Intermittent communication loss (Modbus RTU)
- Resolution Protocol:
mermaidCopy Code
graph LR
A[Check RS485 Termination] --> B[Verify 120Ω resistor at last node]
B --> C[Set Station Address (B01-01≠0)]
C --> D[Confirm Baud Rate (B01-02=19200)]
D --> E[Ground Shield at Drive End Only]
3. Hardware Failure Diagnostics
| Component | Test Method | Pass Criteria |
|---|---|---|
| DC Bus Capacitors | Capacitance meter (discharged!) | ≥90% of 2200μF nominal |
| IGBT Modules | Diode test mode (DMM probes): – P/+ to U/V/W – N/- to U/V/W |
Forward: 0.3-0.7V Reverse: OL |
| Cooling Fan | Amperage check at connector CN5 | 0.18A±10% @ 24VDC |
Safety Notice: Wait ≥5 minutes after power-off and measure DC bus voltage (<25VDC) before touching components.
4. Reset & Recovery Sequence
- Non-Latching Faults (e.g. F04 Underload):
- Press
STOP/RESETkey for 2 seconds
- Press
- Latching Faults (e.g. F11 Overcurrent):
- Cycle control power (≥30 seconds off)
- Initialize parameters: Hold
PROG+DATA/ENTERduring power-up
- EEPROM Corruption (Blank display):
- Reload firmware via Service Port (JTAG adapter TOS-SVC-611 required)
5. Preventive Maintenance Schedule
| Interval | Task | Standard |
|---|---|---|
| Quarterly | Torque terminal screws | Main circuit: 2.0 N·m Control: 0.5 N·m |
| Annually | DC bus precharge resistor check | Resistance: 47Ω ±10% (P/N G9SXA-P47) |
| 30,000 hrs | Electrolytic capacitor replacement | Use only Nichicon UHW series or OEM equivalent |
6. Critical Configuration Checks
- Motor Compatibility:
- Set
A02-01(Motor Poles) correctly (2/4/6/8) A02-02(Rated Current) ≤ Drive’s rated output
- Set
- Braking Unit Settings:
- DC bus threshold
C06-01=760V(for 400V class) - Braking duty cycle
C06-03≤ 10% (continuous)
- DC bus threshold
GPF611S PDF
♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦
Shipping:
1. Your item will be shipped to all countries via EMS, unless one country cannot be shipped via EMS. We will choose DHL, UPS, or FedEx. Please leave us your phone number.
2. We will ship the product to you on the same day or within 1-2 working days after receiving your payment. The shipping time depends on the country/region where you reside, the customs and habits of your country/region, and especially during peak hours.
3. Assuming (assuming) that the item requires payment of tariffs from your country, the buyer is obligated. We are not responsible for any taxes or customs fees in your country/region.
Return Policy:
1. Please contact us before returning the item.
2. The buyer should inform the seller of all returned items within 7 days after receiving the package. We reserve the right to reject any request to inform the seller for more than 7 days.
3. Returned products must have all original packaging and be in good condition.
Response policy:
If you are satisfied with the purchase, please leave us an active response.
2. If you have any questions about the outcome of the transaction or product, please contact us first and we will do our best to satisfy you!
3. Please do not reply with negative feedback before contacting us!