Brand: GE Multilin (GE Vernova Grid Solutions)
Model: 369-HI-R-M-0-0-0-H-E
Product Name: 369 Series Digital Motor Management Relay
Dimensions: 296 mm × 107 mm × 205 mm
Weight: 4.5 kg
Place of Origin: Canada
-
369-HI-R-M-0-0-0-H-E
HS Code: 85364900 (reference for customs declaration, motor protective relay)
Operating Temperature: -40 °C to +60 °C; Storage Temperature: -40 °C to +80 °C
Auxiliary Supply Voltage: Wide high-range input 70-265 V AC / 88-300 V DC, 50-60 Hz; rated power consumption 20 VA
Input: Three-phase current transformer secondary inputs (1 A / 5 A nominal); three-phase voltage potential transformer inputs; 12-channel 3-wire RTD temperature inputs compatible with Pt100, Ni100, Ni120 and Cu10 sensors; multiple galvanically isolated binary status inputs for external interlock, breaker position and auxiliary feedback signals; ground-fault current input supporting measurement frequency range 20-100 Hz.
Output: Four configurable relay contact outputs including main trip output and multi-purpose alarm auxiliary outputs; relay contact rating 8 A at 250 VAC / 30 VDC; non-isolated RS232 local service port; RS-485 Modbus-RTU communication port for host system data exchange.
Core Characteristics and Functions: Comprehensive motor protection covering thermal overload, locked-rotor stall, short-circuit, phase unbalance, phase reversal, earth-fault and under-load detection; built-in dynamic thermal memory model for motor heating-cooling simulation; local front-panel LCD display and keypad for parameter setup, real-time value reading and fault inquiry; waveform capture function for fault-event waveform recording; sequence-of-event logging storing up to 512 historical records; accumulates motor running hours, start-up counts and energy metering data; supports two-speed motor application logic; firmware upgradable via communication port; password-protected parameter modification to prevent unauthorized configuration changes; front-panel IP50 protection rating; conforms to UL, CSA and IEC industrial EMC standards; panel flush-mount design for installation inside motor-control-center cabinets.
-
369-HI-R-M-0-0-0-H-E
-
369-HI-R-M-0-0-0-H-E
♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦
Shipping:
1. Your item will be shipped to all countries via EMS, unless one country cannot be shipped via EMS. We will choose DHL, UPS, or FedEx. Please leave us your phone number.
2. We will ship the product to you on the same day or within 1-2 working days after receiving your payment. The shipping time depends on the country/region where you reside, the customs and habits of your country/region, and especially during peak hours.
3. Assuming (assuming) that the item requires payment of tariffs from your country, the buyer is obligated. We are not responsible for any taxes or customs fees in your country/region.
Return Policy:
1. Please contact us before returning the item.
2. The buyer should inform the seller of all returned items within 7 days after receiving the package. We reserve the right to reject any request to inform the seller for more than 7 days.
3. Returned products must have all original packaging and be in good condition.
Response policy:
If you are satisfied with the purchase, please leave us an active response.
2. If you have any questions about the outcome of the transaction or product, please contact us first and we will do our best to satisfy you!
3. Please do not reply with negative feedback before contacting us!
Related models: