Description
FLOBOSS S600+(17) Parameter Configuration Procedure
I. Pre-Configuration Setup
-
Access Device Interface
- Connect via:
- Local HMI: Use front-panel touchscreen (IP65-rated).
- Remote Access: Use ROC Companion software (v6.1+) or web interface (requires Ethernet/IP setup).
- Log in with Engineer-level credentials (default:
ENGINEER/ENGINEER).
- Connect via:
-
Initialize Configuration
- Navigate:
Main Menu > Configuration > Parameter Setup. - Select
New ConfigurationorEdit Existing(backup current config first).
- Navigate:
II. Core Parameter Settings
(Reference: Section 17 of FLOBOSS S600+ Manual)
| Category | Key Parameters | Recommended Value/Rule | |
|---|---|---|---|
| Flow Measurement | Flow Algorithm |
AGA-8 / GPA 2172 (Gas) / API MPMS Ch. 21.1 (Liquid) | |
Meter Type |
Coriolis / Ultrasonic / Orifice Plate | ||
Units |
MMSCFD, m³/h, BBL/d (align with contract) | ||
| Fluid Properties | Base Temperature |
15°C (59°F) / 60°F (industry standard) | |
Base Pressure |
101.325 kPa / 14.73 psia | ||
Gas Composition |
Configure mole % (C1, CO₂, N₂, etc.) | ||
| Device Communication | Modbus TCP Address |
Unique IP (e.g., 192.168.1.50) | |
HART Polling Interval |
15 sec (default) |
CRITICAL Gas-Specific Settings:
- Enable
Pressure/Temperature Compensation(P/T sensors must be calibrated).- Set
Compressibility Model: GERG-2008 (for natural gas mixtures).
III. Advanced Configuration
-
Alarm Thresholds (
Menu > Alarms > Setpoints)High Flow Alarm: 110% of max operational flowLow Pressure Alarm: <80% normal line pressureSensor Fault Action: Hold last value / Switch to backup
-
Data Logging (
Menu > Data Historian)Scan Interval: 1 sec (high-speed events) / 1 min (standard)Storage Media: Internal SD card (min. 32 GB Class 10) / FTP server
IV. Validation & Commissioning
-
Verify Inputs
- Cross-check P/T sensor readings against calibrated test gauge.
- Confirm fluid properties match assay report (e.g., gas gravity ±0.05%).
-
Functional Test
- Simulate flow conditions using
Test Mode(bypasses actual I/O). - Trigger alarms to validate relay outputs.
- Simulate flow conditions using
-
Save & Lock
- Select
Commit Configuration→ Enter admin password. - Mandatory: Set
Configuration LocktoONto prevent unauthorized changes.
- Select
FLOBOSS S600+(17) PDF
FLOBOSS S600+(17) VIDO
♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦
Shipping:
1. Your item will be shipped to all countries via EMS, unless one country cannot be shipped via EMS. We will choose DHL, UPS, or FedEx. Please leave us your phone number.
2. We will ship the product to you on the same day or within 1-2 working days after receiving your payment. The shipping time depends on the country/region where you reside, the customs and habits of your country/region, and especially during peak hours.
3. Assuming (assuming) that the item requires payment of tariffs from your country, the buyer is obligated. We are not responsible for any taxes or customs fees in your country/region.
Return Policy:
1. Please contact us before returning the item.
2. The buyer should inform the seller of all returned items within 7 days after receiving the package. We reserve the right to reject any request to inform the seller for more than 7 days.
3. Returned products must have all original packaging and be in good condition.
Response policy:
If you are satisfied with the purchase, please leave us an active response.
2. If you have any questions about the outcome of the transaction or product, please contact us first and we will do our best to satisfy you!
3. Please do not reply with negative feedback before contacting us!
More models available: