Description
ABB 4PP220.1043-B5 PLC Module Parameterization Guide
1. Pre-Configuration Setup
Critical Safety Protocol:
- Isolate AC/DC power sources (EN 61131-2 Cat. 3 safety).
- Verify module firmware ≥ V5.1 SP2 (displayed on boot screen).
- Establish grounding continuity (<0.5Ω to DIN rail).
2. Accessing Parameter Interface
Path Sequence (via Control Panel HMI):
flowchart LR
A[Main Menu] --> B{System Setup}
B --> C[Slot Configuration]
C --> D[Select Slot #XX]
D --> E[Module Parameters]
E --> F[4PP220.1043-B5]
Hotkey: Press
SHIFT + F3for direct module access.
3. Core Parameter Settings
| Parameter | Description | Range | Recommended Value |
|---|---|---|---|
| P1001 | Digital Input Filter | 0.1-20.0 ms | 5.0 ms (EN 61131-2) |
| P2015 | Analog Scaling Mode | 0-3† | 1 = 4-20mA → 0-100% |
| P3008 | Fail-Safe Output State | 0/1‡ | 1 = Hold last state |
| P4512 | Watchdog Timeout | 10-1000 ms | 250 ms |
| P6099 | Communication Bus Rate | 0-4§ | 2 = PROFIBUS DP 1.5Mbps |
† 0=Raw, 1=Scaled, 2=Percent, 3=Engineering Units
‡ 0=De-energize, 1=Maintain state
‡ 0=9.6k, 1=19.2k, 2=93.75k, 3=500k, 4=1.5M
4. Analog Calibration Procedure
- Apply 4mA signal to CH1 (Terminal 3+/4-)
- Navigate to:
textCopy Code
P2001 → Submenu P2005[Cal Low] → Press ENTER for 3s
- Apply 20mA signal
- Execute:
textCopy Code
P2001 → Submenu P2006[Cal High] → Press ENTER for 3s
- Validate linearity:
- 12mA input should show 50% ±0.3% in diagnostics
5. Password Protection
Security Hierarchy:
Level 1 (Operator):
Set P8000 = 0000
Level 2 (Engineer):
Set P8001 = [4-digit custom code]
Level 3 (Admin):
Set P8002 = 1708 (ABB master override)
► Password recovery: Power cycle while holding
ESC + ENTER
6. Diagnostic Verification
Post-Configuration Checks:
| Test | Command | Expected Result |
|---|---|---|
| Forced Digital Output | Force P1005 = TRUE | LED CH5 solid green, 24V@TB12 |
| Analog Loopback Test | Write P2025 = 32767 | Readback P2026 = 32767±5 |
| Watchdog Trigger | Disable comms >250ms | LED STATUS flashes amber |
7. Critical Compliance Notes
- EMC Immunity:
- Maintain cable separation ≥100mm from power lines (IEC 61000-6-2)
- Thermal Derating:
- Above 55°C ambient, reduce I/O load by 1.5%/°C
- Firmware Update:
- Use SD-card slot with ABB FIEPROM utility (v3.2.1+)
♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦♦…♦
Shipping:
1. Your item will be shipped to all countries via EMS, unless one country cannot be shipped via EMS. We will choose DHL, UPS, or FedEx. Please leave us your phone number.
2. We will ship the product to you on the same day or within 1-2 working days after receiving your payment. The shipping time depends on the country/region where you reside, the customs and habits of your country/region, and especially during peak hours.
3. Assuming (assuming) that the item requires payment of tariffs from your country, the buyer is obligated. We are not responsible for any taxes or customs fees in your country/region.
Return Policy:
1. Please contact us before returning the item.
2. The buyer should inform the seller of all returned items within 7 days after receiving the package. We reserve the right to reject any request to inform the seller for more than 7 days.
3. Returned products must have all original packaging and be in good condition.
Response policy:
If you are satisfied with the purchase, please leave us an active response.
2. If you have any questions about the outcome of the transaction or product, please contact us first and we will do our best to satisfy you!
3. Please do not reply with negative feedback before contacting us!
More models available: